The DVOP4360V cable is designed to connect an FP0RA21 analog output unit to a MINAS A6SF servo driver, enabling analog signal control for velocity control applications .

Wiring Details:

Connector

Function

Pins

X4 (I/O Connector)

Analog output connection

14-15 (SPR/TRQR/SPL), 29 (SRV-ON), 7 (COM+), 34-35 (S-RDY), 36-37 (ALM)

Key Functions:

  • Analog Speed Command (SPR/TRQR/SPL): 0-10V signal from analog output unit

  • Servo-On (SRV-ON): Energizes the servo motor

  • Servo-Ready (S-RDY): Indicates ready state of the servo driver

  • Alarm Output (ALM): Indicates servo alarm status

The analog input has a resolution of 16 bits with a voltage range of 0V to +/-10V. Additional signals can be transmitted via the same cable to the PLC, including servo ready and alarm status .